Instrument Shielded Cable (2C x 2.5 mm2)

Instrument Shielded Cable (2C x 2.5 mm2)

Conductor: Class 2 multi-strand annealed copper conductor according to IEC 60228.
Insulation: Extruded XLPE compound insulation according to EN 50290-2-29
Shield: Aluminum tape/polyester tape layer shield with 0.5 mm² tinned copper drain wire.
Outer jacket: LSZH compound according to EN 50290-2-27.

Insulation: black
Sheath: black or blue

Physical Property:

İşləmə Temperatur Aralığı (stationary)
Installation Temperature Range (kinematic)
Minimum Bend Radius
UV Protection
Oil-Proof
-30°C – +90°C
7.5 X Outer Diameter
UL 1581 Section 1200
ICEA S-73-532 (Test temperature +60°C for 4 hours. Minimum tensile strength and elongation values of 60% were maintained during the 4-hour period).

Electrical Performance Parameters:

Conductor Cross-Sectional Area (mm2)
0.5
0.75
1
1.3
1.5
2.5
Nominal Insulation Thickness (mm)
0.55
0.55
0.55
0.6
0.6
0.7
Minimum Insulation Thickness (mm)
0.44
0.44
0.44
0.44
0.44
0.53
Conductor Resistance (20°C) Ω/km
36.7
25
18.5
14.2
12.3
7.4
Operating Voltage
Test Voltages
500
Between Cores 2000
Between Core and Screen 2000

Tətbiqlər:

Instrumentation cables in this category are typically used for the transmission of analog and digital signals in instrumentation control systems and should not be connected directly to low impedance power sources, such as public power supply stations. Recommended for indoor and outdoor installations, racks, trays, pipes, wet and dry environments, not recommended for direct burial.

    Zəhmət olmasa, Aşağıdakı Formada Sorğunuzu Verin.


    Abunə ol!