BS 6622 BS 7835 Standard MV Three Core Cable

Three core cable BS 6622 BS 7835 Standard

Leiter: Plain Annealed Copper or Aluminum
Außenjacke: PVC/PE/LSZH
Isolierung: XLPE/EPR
PVC/PE/LSZH outer jacket
PVC/PE/LSZH split sheath (optional)
XLPE/EPR Insulation
Conductor Shield
Adhesive
Armor (optional)

Cable Diameter

Virtual Diameter Under The Armor Layer (mm)
Armored Cable Diameter (mm)
>
<
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15

Physical Characteristics:

Operating Temperature: up to 90°C
Temperature Range: -5°C (PVC jacket); -20°C (PE jacket)
Short-Circuit Temperature: 250°C (maximum duration of short-circuit not exceeding 5s)
Bending Radius: 15 x OD

Rated Voltage Uo/U
Operating Voltage (Um)
Test Voltage (rms)
3.8/6.6KV
7.2KV
6.35/11KV
12KV
25.5KV
8.7/15KV
17.5KV
35KV
12.7/22KV
24KV
51KV
19/33KV
36KV
76KV

Anwendung:

Three-core cables are designed for power distribution from 3.8/6.6KV to 19/33KV at 50Hz.They are mainly used in a variety of applications such as power supply stations, Innenleitungen, outdoor, buried and under water, as well as for the installation of cables to the industry, distribution stations, and power station cables.