CEI 60502 Standard Single Core cables

CEI 60502 standardized single-core power cables

Conductor: Plain annealed copper or aluminum conductor.
Conductor Shielding: Conductor shielding consists of a non-metallic, semiconductor composite extruded layer firmly bonded to the insulation layer, excluding all gaps.
Aislamiento: 1.8/3KV and 3.6/6KV cable ranges are generally insulated with PVC, but also with XLPE, EPR/HEPR.

Conductor/Insulation/Metal Shield
Adhesives
PVC/PE/LSZH Separate Jacket

Physical Properties:

Operating temperature: up to 70°C (PVC insulation); hasta 90°C (XLPE or EPR insulation)
Temperature range: -5ºC (chaqueta de PVC); -20ºC (chaqueta de polietileno)
Short-circuit temperature (duración máxima del cortocircuito no superior a 5 s): 140-160ºC (chaqueta de PVC); 250ºC (chaqueta de polietileno)
Bend radius: 12 x DESDE

Regular Uo/U
In operation (Uno)
Testing (rms)
1.8/3KV
3KV
6.5KV
3.6/6KV
7.2KV
6/10KV
12KV
21KV
8.7/15KV
17.5KV
30.5KV
12/20KV
24KV
42KV
18/30KV
36KV
63KV
21/35KV
42KV
73.5(53)*KV
26/35KV
42KV
91(65)*KV

Cable Structure Parameters:

Sección transversal nominal (mm2)
Unarmored Cable
Armoured Cable
Insulation Nominal Thickness (milímetro)
Copper Strip Thickness (milímetro)
Copper Wire Shield Area (mm2)
Nominal Jacket Thickness (milímetro)
AO Diameter (milímetro)
Approximate Weight (kg/km)
Nominal Pad Thickness (milímetro)
Armor Thickness (milímetro)
AO Diameter (milímetro)
Approximate weight (kg/km)
CU
Alabama
CU
Alabama
10
2.0
0.1
16
1.8
13
240
180
1.2
1.6
1.8
18
460
400
16
2.0
0.1
16
1.8
13
300
200
1.2
1.6
1.8
19
530
430
25
2.0
0.1
16
1.8
15
410
250
1.2
1.6
1.8
20
650
500
35
2.0
0.1
16
1.8
16
510
300
1.2
1.6
1.8
21
780
560
50
2.0
0.1
16
1.8
17
640
350
1.2
1.6
1.8
22
930
640
...
...
...
...
...
...
...
...
...
...
...
...
...
...

Application:

IEC60502 standard power single-core cables are designed for power distribution from 1.8/3KV to 18/30KV at 50Hz. They are mainly used in power supply stations, indoor pipelines, outdoor, underground and submarine water, as well as for the installation of cables to the industry, distribution stations and power stations.

    No dude en enviar su consulta en el siguiente formulario.


    Suscribir!