CEI 60502 Standard Three Core Cables

Cavi a tre nuclei - CEI 60502 Standard

Conduttore: Conduttore semplice in rame ricotto o alluminio.
Conductor shielding: The conductor shielding shall be non-metallic and shall consist of an extruded semi-conductive compound with a semiconductor strip applied on top of the semiconductor compound. The conductor shield is not required for PVC, EPR/HEPR insulated cables in the 1.8/3KV to 3.6/6KV range.
Isolamento: 1.8/3Le gamme di cavi KV e 3,6/6KV sono generalmente isolate con PVC, but can also be insulated with XLPE, EPR/HEPR.

Metal/conductor/insulation shield
Adesivi
Armor (optional)

Round Steel Wire Armored Cable Diameter

Virtual Diameter Under Armor Layer (mm)
Armored Cable Diameter (mm)
>
<
-
10
1.25
10
15
1.25
15
25
1.6
25
35
2.0
35
60
2.5
60
-
3.15

Armor Layer Thickness

Virtual Diameter Under Armor Layer (mm)
Galvanized Steel/Steel (mm)
Aluminum/Aluminum Alloy (mm)
>
<
-
30
0.2
0.5
30
70
0.5
0.5
70
-
0.8
0.8

Proprietà fisiche:

Temperatura operativa: fino a 70°C (Isolamento in PVC); fino a 90°C (Isolamento XLPE o EPR)
Intervallo di temperatura: -5°C (Giacca in PVC); -20°C (Giacca PE)
Temperatura di cortocircuito (maximum duration in case of short-circuit not exceeding 5s): 140-160°C ( PVC sheath ); -40°C ( PE sheath ); -20°C ( PE sheath )
250°C (Giacca PE)
Raggio di curvatura: 15 x DA

Sezione trasversale nominale (mm2)
Cavo non armato
Round Steel Wire Armor
Spessore nominale dell'isolamento (mm)
Spessore della striscia di rame (mm)
Area di schermatura del filo di rame (mm2)
Spessore nominale del rivestimento (mm)
Diametro AO (mm)
Peso approssimativo (kg/km)
Spessore nominale della pastiglia (mm)
Spessore dell'armatura (mm)
Diametro AO (mm)
Peso approssimativo (kg/km)
CU
AL
CU
AL
10
2.0
0.1
16
1.8
23
650
460
1.2
1.6
1.8
28
1480
1290
16
2.0
0.1
16
1.8
24
840
540
1.2
1.6
1.9
29
1720
1410
25
2.0
0.1
16
1.8
26
1160
680
1.2
1.6
1.9
32
2130
1650
35
2.0
0.1
16
1.8
29
1490
820
1.2
2.0
2.1
36
2810
2140
50
2.0
0.1
16
1.9
32
1900
1000
1.2
2.0
2.2
39
3340
2450
...
...
...
...
...
...
...
...
...
...
...
...
...
...

Applicazione:

Three-core cables are designed for power distribution from 3.6/6.6KV to 19/33KV at 50Hz. They are mainly used in a wide range of applications such as power supply stations, condotti interni, all'aperto, buried and in water, così come per l'installazione di cavi per l'industria, distribution stations, and power station cables.

    Non esitate a fornire la vostra richiesta nel modulo sottostante.