BS 6622/BS 7835 Standard Single-Core MV Cables

BS 6622 BS 7835 standard single core medium-voltage power cables

導体: Plain Annealed Copper or Aluminum
アウタージャケット: PVC/PE/LSZH
絶縁: XLPE/EPR

Insulation Layer Parameters:

Nominal Cross Section
Thickness of Insulation at Nominal Voltage
3.8/6.6KV (Um=7.2KV)
6.35/11KV (Um=12KV)
8.7/15KV(Um=17.5KV)
12.7/22KV(Um=24KV)
19/33KV(Um=36KV)
mm2
んん
んん
んん
んん
んん
70 185
2.5
3.4
4.5
5.5
8.0
240
2.6
3.4
4.5
5.5
8.0
300
2.8
3.4
4.5
5.5
8.0
400
3.0
3.4
4.5
5.5
8.0
≥500
3.2
3.4
4.5
5.5
8.0

Physical Characteristics:

Operating Temperature: up to 90°C
Temperature Range: -5°C (PVC jacket); -20°C (PE jacket)
Short-Circuit Temperature: 250°C (maximum duration of short-circuit not exceeding 5s)
Bending Radius: 12 x OD

Rated Voltage Uo/U
Operating Voltage (Um)
Test Voltage (rms)
3.8/6.6KV
7.2KV
6.35/11KV
12KV
25.5KV
8.7/15KV
17.5KV
35KV
12.7/22KV
24KV
51KV
19/33KV
36KV
76KV

APPLICATION:

The standard power single-core cables have a voltage range from 3.8/6.6KV to 19/33KV and a frequency of 50Hz. they are mainly used in a variety of places such as power supply stations, indoor and outdoor laying, in pipelines and tunnels, in mines and shafts, in direct burial in the soil and underwater at the bottom of the sea, 等. They are capable of withstanding considerable pressures and mechanical external forces, and axial tensile forces.

    下記フォームよりお気軽にお問い合わせください.


    申し込む!