VDE 0276 Standard MV Single Core Cables

Single-Core Cables - VDE 0276 Standard

導体: Stranded round copper or aluminum conductor
Conductor shielding: The conductor shielding consists of a non-metallic extruded layer of semiconductor composite layers tightly wrapped around an insulating layer to exclude internal gaps.
絶縁: Extruded XLPE-2XI1 type compound according to DIN VDE 0207 part 22 and HD 620.1.

Glues
XLPE Insulation
Conductor/Insulation/Metal Shield
PVC/PE/XLPE Split Sheath (optional)

Voltage Level:

Rated Voltage Uo/U
Operating Voltage (max)
Testing Voltage
3.6/6KV
8KV
10KV
6/10KV
12KV
15KV
8.7/15KV
18KV
22.5KV
12/20KV
24KV
30KV
18/30KV
36KV
45KV

Physical Characteristics:

Operating temperature: up to 90°C
Temperature range: -5°C (PVC jacket); -20°C (PE jacket)
Short-circuit temperature: 250°C (maximum duration of short-circuit not exceeding 5s)
Bend radius: 15 x OD (non-metallic sheath)
30 x OD (aluminum jacket)

Cable Structure Parameters:

Nominal Cross Section mm²
Insulation Nominal Thickness mm
Copper Strip Thickness mm²
Copper Wire Shield Area mm
Nominal Jacket Thickness
Approximate Outside Diameter
Approximate Weight kg / km
N2XSY/N2XSH Cu
NA2XSY/NA2XSH Al
N2XS2Y Cu
NA2XS2Y Al
N2XS (F) 2Y Cu
NA2XS (F) 2Y Al
25
2.0
0.1
16
1.4
13
500
180
480
140
500
230
35
2.0
0.1
16
1.4
14
620
280
600
240
620
330
50
2.0
0.1
16
1.4
15
700
380
750
290
750
430
70
2.0
0.1
16
1.5
17
900
480
800
380
1000
560
95
2.0
0.1
16
1.5
19
1200
590
1050
460
1300
670
120
2.0
0.1
16
1.6
21
1450
700
1300
550
1500
800
150
2.0
0.1
25
1.6
22
1700
800
1550
650
1800
900
...
...
...
...
...
...
...
...
...
...
...
...

アプリケーション:

Power single-core cables with voltage ranging from 3.8/6.6KV to 19/33KV and frequency of 50Hz are mainly used in power supply stations, indoor and outdoor laying, pipelines, tunnels, mines, shafts, direct burial in the soil and underwater, 等. They are able to withstand considerable pressure and mechanical forces, axial tensile force.

    下記フォームよりお気軽にお問い合わせください.