VDE 0276 Standard MV 3 Core Cables

MV 3 core cables - VDE 0276 standard

Conductors: Stranded round copper or aluminum conductors according to IEC 60228, VDE 0276 Class 2 / VDE 0295 HD 383.
Conductor shield: Semiconductor composite layer consisting of a non-metallic extruded layer, tightly wrapped with an insulating layer to exclude internal gaps.
Insulation: Extruded XLPE-2XI1 type compound according to DIN VDE 0207 part 22 and HD 620.1.

PVC/PE/LSZH outer jacket
PVC/PE/LSZH split sheath (optional)
Metal/insulation/conductor shield
Adhesive
Armor (optional)

Voltage Level:

Rated Voltage Uo/U
Operating Voltage (max)
Testing Voltage
3.6/6КВ
8КВ
12.5КВ
6/10КВ
12КВ
21КВ
8.7/15КВ
18КВ
30.5КВ
12/20КВ
24КВ
42КВ
18/30КВ
36КВ
63КВ

Physical Characteristics:

Operating temperature: up to 90°C
Temperature range: -5°С (PVC jacket); -20°С (PE jacket)
Short-circuit temperature: 250°С (maximum duration of short-circuit not exceeding 5s)
Bend radius: 15 x OD (non-metallic sheath)
30 x OD (aluminum jacket)

Cable Structure Parameter: Take the example of N2XSEY NA2XSEY

Nominal Cross Section (mm²)
Approximate Conductor OD (мм)
Insulation Nominal Thickness (мм)
Copper Strip Thickness (мм)
Copper Wire Shield Area (mm²)
Approximate Insulation OD (мм)
Nominal Jacket Thickness (мм)
Approximate Outside Diameter (мм)
25
6.05
2.5
0.1
16
12.5
1.5
37
35
7.10
2.5
0.1
16
13.5
1.6
39
50
8.25
2.5
0.1
16
14.7
1.6
42
70
9.90
2.5
0.1
16
16.3
1.7
46
95
11.7
2.5
0.1
16
18.1
1.7
50
120
13.1
2.5
0.1
16
19.5
1.8
53
150
14.3
2.5
0.1
25
20.7
1.8
56
185
16.3
2.5
0.1
25
22.7
1.9
60
...
...
...
...
...
...
...
...

Applications:

Three-core power cables have a voltage range from 3.8/6.6KV to 19/33KV and a frequency of 50Hz, and are mainly used in power supply stations, indoor and outdoor laying, pipelines, туннели, mines, shafts, direct burial in the soil and underwater, и т.п., and are able to withstand considerable pressure and mechanical forces, axial tensile force.